Air destratification fans: when to install them

By International Horizon DevelopmentPublished on 7 min read

Share this article

A large industrial workshop at blue hour: cylindrical destratification fans hang beneath the steel roof structure, above a lit concrete floor and workstations.

Why heat builds up under the roof

In a heated high-ceilinged space, warm air rises and accumulates under the roof. This effect is called stratification. Occupants work near the floor, where the air is coldest, while the warmest air sits under the ceiling.

The consequence is twofold. The heating must run longer to hold the set point at workstation level. And the heat that builds up at high level escapes more easily through the roof.

An air destratification fan is a device that evens out the temperature of a space by bringing this heat back down to the floor. The standardised operation sheets of the French energy savings certificate scheme (CEE) define it precisely: it redistributes the heat near the ceiling or ridge, supplies no heat of its own, and remains independent of the heating system.

Two sheets fund this operation, in their version A71-4 applicable since 1 August 2025:

SheetSectorTitle
BAT-TH-142Existing commercial buildingAir destratification system
IND-BA-110Existing industrial buildingDestratification fan or air circulator

Both sheets apply to operations committed before 1 August 2030. Their conventional lifetime is 15 years.

Where destratification makes sense

Destratification works in a high, enclosed and heated volume. The sheets turn this logic into eligibility conditions.

The space must have a height under the ceiling or ridge of at least five metres. It must be fully enclosed. It must be heated by a convective system, a radiant system, or both.

The sheets give examples of each family. A convective system heats the air: air handling unit, rooftop unit, unit heater, warm air generator or fan coil unit. A radiant system heats surfaces and people: radiant cassettes, tubes and panels, or underfloor heating.

In practice, the profiles most concerned are production workshops, heated industrial halls, gymnasiums, sports halls, high-ceilinged retail spaces and some entrance halls. The eligibility of each space is checked against its actual characteristics: height, use, heating system and temperature set point.

Exclusions to know before any project

Three exclusions rule out certain spaces from the outset, in both sheets.

ExclusionWhat BAT-TH-142 and IND-BA-110 say
Storage areasLogistics warehouses, stockrooms, warehouses and storage areas are excluded
Low-heated spacesSpaces whose occupied heating set point is strictly below 15 °C are excluded
Ceiling fansCeiling-mounted air circulation fans are not eligible

The exclusion of warehouses is part of a wider trend. A draft order put to consultation in October 2026 proposes to extend this exclusion to other commercial-building sheets, as we explain in our article on warehouses excluded from CEE sheets.

An exclusion is judged on the actual use of the space, not on its label. A building that combines production and storage calls for a space-by-space analysis. The heated production area may remain eligible, while the adjoining stockroom is not. The site plan and the description of uses must therefore be clear from the study stage.

The technical requirements of both sheets

The sheets distinguish two technologies.

In vertical-flow destratification, air is drawn in at high level, within the top fifth of the height of the space. It is sent back down to the floor.

In horizontal-flow destratification, the layers of air are drawn in over the full height of the space, then mixed. The flow travels horizontally between a diffuser and a collector.

Several requirements are common to both technologies and both sheets. Air speed must not exceed 0.2 m/s one metre above the floor, to protect occupant comfort. The system is controlled by at least one air temperature measurement taken at high level. Installation is carried out by a professional covered by ten-year liability insurance for electrical work.

One difference separates the two sheets. BAT-TH-142 requires the noise level of the system alone to be strictly below 45 dB(A). IND-BA-110 does not include this acoustic criterion.

The sizing report, the core of the file

Both sheets require destratification needs to be determined by a sizing report and a layout plan. The layout plan shows the precise position of the equipment in the space.

This report is drawn up by a professional or an engineering office holding OPQIBI qualification 1327, OPQIBI 1905 for commercial buildings or OPQIBI 1717 for industry, or carrying out its studies under the energy audit frameworks cited by the sheet. It is dated and signed by its author and by the beneficiary, who thereby validates the assumptions used.

The sheet makes it the specific supporting document for the operation. The number of devices installed must be consistent with its recommendations. An imprecise report, or a gap between the report and the installation, therefore weakens the whole file.

This is where the expertise of an independent engineering office makes the difference. Sizing must take account of the volume, the heating system, the existing ventilation and the use of the space. A poorly positioned device can create draughts with no real benefit for occupants.

How the certificate amount is calculated

The CEE amount covers the whole enclosed and heated space concerned by destratification. It equals a flat rate in kWh cumac per kW, multiplied by the rated output of the space's heating system.

The flat rate depends on the climate zone and on the type of heating:

Climate zoneBAT-TH-142, convectiveBAT-TH-142, radiantIND-BA-110, convectiveIND-BA-110, radiant
H13 9001 4007 2002 500
H24 5001 6008 0002 800
H34 6001 6008 5003 000

The flat rates are expressed in kWh cumac per kW of heating output.

Three rules complete the calculation. The output used is the sum of the rated outputs of the equipment that heats the space. If a boiler heats several spaces, its output is allocated in proportion to the heated volumes. When a space combines convective and radiant heating, the amounts for both types add up.

The flat rates show that destratification earns more with convective heating, which heats the air, than with radiant heating. They are also higher in industry than in commercial buildings.

What it means for you

For a manufacturer

A high, enclosed workshop heated by unit heaters or an air handling unit is often the most favourable case. Sheet IND-BA-110 offers the highest flat rates. The first check concerns the boundary between production and storage areas.

For a commercial building manager

A gymnasium, a retail space or a high-ceilinged hall may fall under BAT-TH-142. The 45 dB(A) acoustic criterion matters here, because the space is occupied by the public or by staff.

For an installer

The installation must follow the sizing report. The proof of completion must state the items required by the sheet, including the direction of the airflow, the air speed one metre above the floor and the output of the space's heating.

For an obligated party or a delegated party

The sheet makes the sizing report the specific supporting document for the operation. Its consistency with the installation and with the actual use of the space determines how robust the file is.

Our recommendations

Before any quotation, check three points: the actual height of the space, its use and its heating system. On their own, they decide eligibility.

Destratification is often part of a wider review of a site's heating. Our guide to sizing collective heat pumps shows the same rigour applied to heat production. Our guide to energy savings certificates sets out how the French scheme works.

IHD's engineering office produces independent destratification sizing reports and layout plans, for commercial and industrial buildings, through to the valorisation of the certificates. Discover our energy audit and engineering offer, or contact us to review your building.

Frequently asked questions

What is an air destratification fan?

It is a device that evens out the temperature of a space by redistributing the heat near the ceiling or ridge down to floor level. According to sheets BAT-TH-142 and IND-BA-110, it supplies no heat of its own and remains independent of the heating system.

What minimum height is required for destratification funded by CEE certificates?

Sheets BAT-TH-142 and IND-BA-110 require a height under the ceiling or ridge of at least five metres. The space must also be fully enclosed and heated by a convective system, a radiant system or both.

Can a warehouse qualify under sheet BAT-TH-142?

No. Logistics warehouses, stockrooms, warehouses and storage areas are excluded from sheets BAT-TH-142 and IND-BA-110. Spaces whose occupied heating set point is strictly below 15 °C are also excluded.

Is a ceiling fan eligible?

No. Both sheets state that ceiling-mounted air circulation fans are not eligible. Only vertical-flow or horizontal-flow destratification systems that meet the conditions of the sheet give rise to certificates.

How is the CEE amount for destratification calculated?

The amount in kWh cumac is a flat rate per kW, set by climate zone and by whether the heating is convective or radiant, multiplied by the rated output of the space's heating system. The two types add up when a space combines both kinds of heating.

Until when do sheets BAT-TH-142 and IND-BA-110 apply?

Under their version A71-4, both sheets apply to operations committed before 1 August 2030. Their conventional lifetime is 15 years.

Sources

Every fact in this article refers to one of these sources, consulted on the date shown.

  1. 01
    BAT-TH-142 vA71-4 à compter du 01-08-2025 : Système de déstratification d'air

    Ministère chargé de l'énergie (DGEC) — published on

  2. 02
    IND-BA-110 vA71-4 à compter du 01-08-2025 : Déstratificateur ou brasseur d'air

    Ministère chargé de l'énergie (DGEC) — published on

  3. 03
    Projet d'arrêté portant modification de fiches d'opérations standardisées (page de consultation)

    Ministère de la Transition écologique — consultations publiques — published on

Is your project affected?

We read the text that applies to your file, in the version in force, before any sizing.

See the six markets we analyse

Share this article